Chiller Vibration Isolator Spring Mount 25mm Deflection: When the Standard Fails

Chiller Vibration Isolator Spring Mount 25mm Deflection: When the Standard Fails

Twenty-five millimetres is the correct chiller default, but it is wrong for screw chillers with strong low-speed components and for any tall chiller with a high centre of gravity. The phrase "chiller vibration isolation spring mount 25mm deflection" appears in so many specifications that it has become a reflex rather than a calculation. Brothers manufactures chiller mounts for OEM packages and bulk plant-room orders, and the two cases below account for most of the revisions we are asked to make.

A Spring Vibration Isolator under a chiller has one job: hold the assembly's natural frequency below the compressor's exciting frequency. Which compressor you have changes that frequency by an order of magnitude, and the boilerplate does not know which one is on your drawing.

 


 

1. Is 25 mm enough for every chiller type?

No — centrifugal chillers are fine at 25 mm, screw chillers often need 38–50 mm, and reciprocating chillers need the most of all.

The reason is the spectrum, not the weight. A centrifugal compressor running at 3,000–3,600 RPM produces a dominant tone at 50–60 Hz, which is easy to isolate. A screw compressor turns much slower and adds a strong low-frequency component from rotor meshing. A reciprocating compressor adds a once-per-revolution imbalance that can sit below 10 Hz. Same tonnage, same footprint, three completely different isolation problems.

Compressor type Dominant exciting frequency Recommended deflection Natural frequency Inertia base
Centrifugal, 3,000–3,600 RPM 50–60 Hz 25 mm 3.15 Hz Only if CG is high
Screw, low-speed component 15–30 Hz 38–50 mm 2.23–2.56 Hz Recommended
Reciprocating 8–15 Hz 50–75 mm 1.82–2.23 Hz Required
Absorption / low-speed < 8 Hz Air spring < 1.5 Hz Required

Screw chiller vs centrifugal chiller vibration frequency is therefore the first question on a selection sheet, not an afterthought. At 15 Hz a 25 mm mount gives a frequency ratio of 4.76 and 95.4% efficiency — acceptable on a slab, marginal above an occupied floor. At 8 Hz on a reciprocating unit, 25 mm gives r = 2.54 and only 81.6%, which will not pass a structure-borne noise criterion in a hotel or hospital.

The second failure mode is rigidity of the connections. Chiller vibration isolation fails more often at the pipework than at the mount: flexible rubber expansion bellows are required on chilled water, condenser water and refrigerant lines, and the first several pipe hangers off the machine must be resilient. A Damping Vibration Damper on those lines prevents the isolation from being bypassed by a rigid path. The Water Pump Vibration Isolator feeding the chiller is a separate calculation at the pump's own 1,500 or 1,750 RPM — typically 10–13 mm, not 25 mm.

Brothers publishes spring rate and rated deflection for each chiller mount so that custom selections can be checked at the real operating load. That matters here because chillers are often quoted at shipping weight, while the springs are loaded at operating weight plus charge — a difference that moves the deflection off the specified value. For OEM / ODM projects we issue factory test data with each wholesale batch.

✅ Bottom line: Use 25 mm for centrifugal machines; step to 38–50 mm for screw and 50–75 mm for reciprocating, then verify at operating weight.

 


 

2. When is an inertia base actually required?

When the chiller's centre of gravity is high enough that the unit can rock on its springs, or when the machine generates large start-up torque.

An inertia base is a concrete-filled steel frame between the chiller and the isolators. It does not isolate anything — the springs do that. It adds mass to lower the combined CG, reduces the amplitude of rocking, and gives a rigid platform so the machine frame is not asked to span between individual mounts.

Inertia base for chiller concrete weight ratio is usually 1.5–2.5 times equipment weight. For a 6,000 kg chiller, a 9,000–15,000 kg base brings the total to 15,000–21,000 kg, which roughly doubles the load per isolator and typically moves the selection into a higher model band. Skip that step in the calculation and the mounts arrive under-rated.

The decision checklist:

  • Tall or narrow units. A vertical chiller or a tall packaged unit with a high CG rocks at start-up. Base recommended.
  • Reciprocating compressors. High torque and strong low-frequency imbalance. Base required.
  • Upper floors. Where the slab is flexible, the added mass stabilises the coupled system. Base recommended.
  • Direct-drive centrifugal on grade with a low, wide frame. Usually no base needed — the frame itself is stiff enough.
  • Never confuse a housekeeping pad with an inertia base. A concrete plinth under the isolators is part of the structure and isolates nothing.

The base also changes the support layout. Keep the isolators at the equipment manufacturer's designated lift points; adding extra mounts between them puts the frame into bending it was not designed for. Six points is generally better than four above 2,000 kg, because it reduces sensitivity to a CG that is not where the drawing said. Set every levelling bolt so the compression at each point agrees within 10–15%.

One more item belongs in the submittal: a Spring Vibration Isolator schedule keyed to equipment tags, with rated load, deflection, spring rate and anchor details. Most Section 23 05 48 specifications ask for exactly that, plus a deflection verification at handover. Brothers supplies the schedule as part of its custom submittal package for China manufacturer bulk orders.

✅ Bottom line: Add an inertia base when CG or start-up torque causes rocking; size the springs for equipment plus base mass, not equipment alone.

 


 

FAQ

Q: Can I use a 25 mm mount on a screw chiller if the floor is slab-on-grade? A: You can, but expect around 95% at 15 Hz and less if the low-speed component falls to 10 Hz. On grade that is often acceptable. On an upper floor above occupied space, move to 38 mm — the extra height is cheaper than a post-commissioning noise investigation.

Q: How do I verify the deflection after installation? A: Measure the free height of each spring before loading and the compressed height at operating weight. The difference is the actual static deflection. It should be within roughly 10% of the specified value, and consistent across all mounts. A spring bottomed out or barely compressed means the load distribution is wrong.

Q: Do I need restrained springs for a chiller in a seismic zone? A: Where the local code applies — IBC / ASCE 7 in the US, for example — equipment above the stated weight threshold in higher seismic design categories needs restrained isolators, and some jurisdictions require shaker-table certification. Check the project's seismic design category before selecting; restrained mounts need to be specified at tender stage, not substituted on site.

 


 

Free chiller mount and base calculation

Send compressor type, operating weight, RPM, CG height, support points and floor level. Brothers will return a deflection recommendation, a base-mass calculation and an isolator schedule keyed to your equipment tags — free within 24 hours. Brothers Shock Absorber Co., Ltd. is a China manufacturer of Spring Vibration Isolator, Water Pump Vibration Isolator and Damping Vibration Damper products, with OEM / ODM support and wholesale pricing. Brothers issues the isolator schedule in the project tag format.